Chapter 2 System Installation
1-68
2
Visual KV
Series
2.1 Installation Environment
Wiring for a DC type basic unit
For a DC type basic unit, perform the wiring as shown in the figure below.
Note: Connect the power supply to the power supply input terminals with 24 VDC
output, which offers a sufficient margin of power capacity. Usually, the sum of the
current consumption of all connected units multiplied by 1.5 or more is required for
the power capacity.
Cautions on wiring for I/O units
When performing wiring for an I/O unit, pay strict attention to the following contents.
Separate input lines from output lines in wiring.
If the wiring for power is located near I/O signal lines, a malfunction may occur
caused by the effects of a high voltage and large current.
Keep I/O signal lines away from the power wiring by at least 100 mm.
Separate 24 VDC I/O lines from 100 VAC and 200 VAC lines.
When using pipes for wiring, make sure that the pipes are securely grounded.
When I/O signal lines cannot be separated from the wiring for power
In such a case, perform grounding on the KV side using batch-shielded cables.
(In some environments, grounding should be performed on the reverse side of the
KV.)
Terminal
The terminal screws used are M3. When performing wiring with crimp-style termi-
nals, use the following ones.
KV-10DR
0123
012345
5ch
0ch
C1
001 002 003 004 005
C2
KV-10DR
50024V-IN-OV C3 C4 503
501 502
000
IN
OUT
EYENCE
24 VDC
external power
supply
Breaker
RL
24 VDC
KV
Input
Shielded cable
Sensor
Output
Ground
Unit: mm
6.0 maximum
M3
6.0 maximum
KVHKA Chap 02.p65 08.3.11, 11:11 AM68