7.6 Display Interface Mode Programming
KV-300 Series Only
KV-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-273
1
7
7.6.2 Command and Response Format
The format for commands and responses is as follows.
Format used when sending a command of 132 characters or more
1. First transmission data (131 characters max.)
2. Intermediate data transmission (128 characters max.)
3. Last transmission data (128 characters max.)
Note 1: When a command is divided into several segments for transmission, the first
and intermediate segments end with the delimiter (CR) instead of the terminator.
Note 2: When dividing a write command such as WR, WL, WH, WC, and WD, into
segments, do not divide a 4-character data for a same channel. Divide data by a 4-
character data for a channel.
Communication procedure when dividing a command into segments and sending
them sequentially
@ xxxx xx❋
C
R
Station no. (00 to 15)
Header code
Text (122 characters max.)
FCS
Terminator
FCS calculation range
@ XXXX XX
C
R
Station no. (00 to 15) Header code
Text no. 1 (123 characters max.) FCS
Delimiter
FCS calculation range
Text no. 2 (125 characters max.)
XX
C
R
FCS
Delimiter
FCS calculation range
Text no. 3 (124 characters max.)
XX
❋
C
R
FCS
Terminator
FCS calculation range
KVHKA Chap 07_5to10.p65 08.3.11, 11:18 AM273
Comentarios a estos manuales