7.8 Troubleshooting Guide
KV-300 Series Only
KV-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-305
1
7
7.8.2 Precautions
Environmental requirements
When installing the KV-L2, note the following:
Avoid exposure to direct sunlight.
Avoid exposure to temperatures below 0°C (32°F) or exceeding 50°C (122°F).
Avoid exposure to humidity below 35%RH or exceeding 85%RH.
Avoid areas where condensation occurs due to sudden drops in temperature.
Avoid exposure to corrosive or flammable gases.
Avoid exposure to airborne dust, metal particles, oil, or corrosive substances
such as salt.
Avoid exposure to strong vibration or impact.
Avoid locations where water, oil, or chemicals may splash the KV-L2.
Avoid exposure to strong magnetic or electrical fields.
Panel installation
Consider accessibility and environmental resistance when installing the KV-L2 inside
a panel.
Ambient temperature
The operating temperature range of the KV-L2 is 0 to 50°C (32 to 122°F) (No freez-
ing).
Provide enough space for proper ventilation. If the temperature exceeds 50°C
(122°F), provide a fan or air conditioner.
Improving noise resistance
Do not install the KV-L2 and high voltage equipment in the same control panel.
Isolate the KV-L2 as far as possible from power cables.
Access
Isolate the KV-L2 as far as possible from high voltage equipment and drive equip-
ment in order to ensure safe and easy access for adjustment and maintenance.
Wiring
The KV-L2 terminal block includes M3.0 screws.
Use the following types of crimp terminals.
6.0 max.
6.0 max.
KVHKA Chap 07_5to10.p65 08.3.11, 11:18 AM305