7.7 Non-procedure Mode Programming
KV-300 Series Only
KV-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-292
7
7.7 Non-procedure Mode Programming
7.7.1 Operating in Non-procedure Mode
Communications protocol
In non-procedure mode, the KV-L2 can be connected to an external device having
an RS-232C or RS-422A terminal to write a series of text data (100 bytes maximum)
into data memory as a batch and to send text data from data memory to a connected
device.
Setting of the communications protocol and connection of the KV-L2 to an external
device are described below.
Setting the operation mode
Set the operation mode using the operation mode setting switch SET A (A1 to A4).
Use A1 and A2 to set the mode for port 1, and A3 and A4 to set the mode for port 2.
Turn OFF the power switch before setting the operation mode.
Set the operation mode setting switch A1 to A4 as above.
Setting the communications protocols
Set the baud rate, data bit length, parity, and stop bit with communications protocol
setting switch SET B (B1 to B8) according to the specifications of the external device
to be connected. Turn OFF the power switch before setting the switches.
ON
OFF
A1 A2 A3 A4
Operation mode Port 1 Port 2
A1 A2 A3 A4
KV mode OFF OFF OFF OFF
Display Interface mode OFF ON OFF ON
Non-procedure mode ON ON ON ON
ON
OFF
B1 B2 B3 B4
B5 B6 B7 B8
B1 B2 B3 B4 B5 B6 B7 B8
Baud rate 1200 bits/s OFF OFF OFF OFF
2400 bits/s ON OFF OFF OFF
4800 bits/s OFF ON OFF OFF
9600 bits/s ON ON OFF OFF
19200 bits/s OFF OFF ON OFF
31250 bits/s ON OFF ON OFF
8400 bits/s OFF ON ON OFF
Setting disabled ON ON ON OFF
Parameters Data bits 7 bits OFF OFF
8 bits ON OFF
Parity None OFF OFF OFF
Odd ON OFF OFF
Even ON ON OFF
Stop bit 1 bit OFF OFF
2 bits ON OFF
KVHKA Chap 07_5to10.p65 08.3.11, 11:18 AM292