9.5 Programming Examples
KV-10/80 Series Only
KV-300
KV-10/80
Chapter 9 KV-AD4/DA4 Analog I/O Unit
1-365
1
9
Outputting Analog Input Data
This sample program outputs data received from the analog inputs.
Note: Voltage can be converted to current, and vice versa by switching the I/O
wiring.
Conditions
Analog data is input from analog input V0 on the KV-AD4.
(The digital data of data memory DM0992 is used for this operation.)
The data that was input from analog input V0 is output as it is to analog output
V0 on the KV-DA4. (The digital data is written to data memory DM0996.)
Ladder diagram
1. DM0996 is initialized when the power is turned ON.
(That is, #2000 is written to DM0996.)
2. Digital data in data memory for A/D conversion is written to DM0001.
3. Before the digital data is written to data memory for D/A conversion, check that
the data is #4095 or less.
Note: An unsteady value will be output if a value outside the range 0 to 4095 is
written to data memory for D/A conversion.
4. The output data will be updated at the rising edge of special utility relay 2800. (As
internal relay 1000 switches ON/OFF at each scan, the output data will be
updated every two scans.)
2008
#02000
LDA
2007
DM0992
LDA
1000
DM0996
STA
DM0001
STA
1500
1000
1000
2800
1500
2002 2011
DM0001
LDA
#04095
CMP
DM0001
LDA
DM0996
STA
1
2
3
4
( )
( )
( )
KVHKA Chap 09.p65 08.3.11, 11:20 AM365