8.3 Installation
KV-300 Series Only
KV-300
KV-10/80
Chapter 8 KV-AN6 Analog I/O Module
1-319
1
8
8.3.5 Setting I/O Ranges
This section describes how to set the KV-AN6 I/O ranges.
As shown in the following figure, the analog input (A/D) range and analog output (D/
A) range can be selected with the slide switches on the right side of the KV-AN6
module.
The I/O ranges are factory-set to ±5 V.
Analog input (A/D) range Analog output (D/A) range
Selection Setting Selection Setting
switch switch
Voltage input: -5 to +5 V Voltage output: -5 to +5 V
Voltage input: -10 to +10 V Voltage output: -10 to +10 V
Current input: 0 to 20 mA
Connecting Current output: 4 to 20 mA
terminal for
current output
CAUTION
±10V 0 to 20 mA±5V
±5V ±10V
Analog output range (D/A)
selection switch
Analog input range (A/D)
selection switch
KV-AN6
module
CH0
CH1
CH4
CH5
CH2
CH3
A
/
D
D
/
A
Turn OFF the power switch before changing selection switch settings.
Analog input signals must fall within the range set by the selection switch.
KVHKA Chap 08.p65 08.3.11, 11:19 AM319