Chapter 2 System Installation
1-65
1
2
Visual KV
Series
2.1 Installation Environment
2.1.2 Installation Position
Installation direction
When attaching a unit inside a panel, install the unit so that the front face (equipped
with the Access Window, communication ports, etc.) faces front or upwards.
Distance between adjacent panels/equipment
When installing a unit, keep the distances shown below between the panel or
equipment so that the power supply can release heat.
Note 1: If the temperature inside the panel exceeds 50°C, which is specified as the
maximum ambient operating temperature, then install heat exchangers, etc. to
reduce the temperature.
Note 2: Ensure sufficient ventilation space so that the power supply can release
heat.
Note 3: Never install a unit just above any equipment which generates a lot of heat.
Installation on ceiling
Incorrect
Upward installation *
Correct
20 mm
20 mm
10 mm
Unit
Vertical installation
Incorrect
Front installation
Correct
* Upward installation does not
comply with CE marking.
KVHKA Chap 02.p65 08.3.11, 11:11 AM65