9.5 Programming Examples
KV-10/80 Series Only
KV-300
KV-10/80
Chapter 9 KV-AD4/DA4 Analog I/O Unit
1-363
1
9
Example 2: Outputting Analog Current (4 to 20 mA)
Data that has been written to DM0000 is converted to digital data for analog
output.
The digital data is sent to analog output I0 on the KV-DA4.
(Digital data is written to data memory DM0996.)
•4 mA is output when input 0000 is ON.
20 mA is output when input 0000 is OFF.
1. #4000 is written to DM0000 when input 0000 is ON.
2. #20000 is written to DM0000 when input 0000 is OFF.
3. ((DM0000
÷ 4 µA) - 1000) is calculated, and the calculation result is written to
DM0001.
4. Before the digital data is written to data memory for D/A conversion, check that
the data is #4095 or less.
Note: An unsteady value will be output if a value outside the range 0 to 4095 is
written to data memory for D/A conversion.
5. The output data will be updated at the rising edge of special utility relay 2800. (As
internal relay 1000 switches ON/OFF at each scan, the output data will be
updated every two scans.)
Note: In the case of current output, DM0996 need not be initialized (#2000 written to
DM0996) when the power is turned ON.
0000
#04000
DW
0000
DM0000
#20000
DM0000
DW
2002
DM0000
LDA
#00004
DIV
DM0001
STA
#01000
SUB
1000
1000
1000
2800
2002 2011
DM0001
LDA
#04095
CMP
DM0001
LDA
DM0996
STA
1
2
3
4
5
( )
( )
KVHKA Chap 09.p65 08.3.11, 11:20 AM363