9.2 Configuration
KV-10/80 Series Only
KV-300
KV-10/80
Chapter 9 KV-AD4/DA4 Analog I/O Unit
1-338
9
Analog input terminal assignment
Terminal Description
• Input range: -10 to +10 V
• The channel to input from is set by
the selector switch.
Ground for analog signal (connected internally)
I0
I1
I2
I3
Analog voltage input ch3
Signal
Analog voltage input ch0
Analog voltage input ch1
Analog voltage input ch2
Analog current input ch0
Analog current input ch2
Analog current input ch1
Analog current input ch3
NC (No connection)
C1
C2
C3
C4
C5
C6
C7
C0
V0
V1
V2
V3
• Input range: 4 to 20 mA
• The channel to input from is set by
the selector switch.
Note: Do not connect the input voltage and input current to terminals of the same
No., for example, by connecting external instruments to both V0 and I0. Doing so
might cause the KV-AD4 to malfunction.
Do not simultaneously connect the current and voltage (V0 and I0,V1 and I1,V2
and I2,V3 and I3) of the same channel to external instruments. Doing so might
cause the KV-DA4 to malfunction.
Dimensions
CAUTION
C0 C1 C2 C3
C4 C5 C6 C7
V0 V1 V2 V3
I0 I1 I2 I3
ANALOG IN
KEYENCE
KV - AD4
POWER
2-
ø
5 (mounting hole)
99
31
65
39
43
35.4
90
111
KVHKA Chap 09.p65 08.3.11, 11:20 AM338