9.4 Programming
KV-10/80 Series Only
KV-300
KV-10/80
Chapter 9 KV-AD4/DA4 Analog I/O Unit
1-350
9
9.4 Programming
9.4.1 Programming the KV-AD4
This section describes the A/D conversion mechanism, and the digital data that is
written to the CPU by the KV-AD4 after A/D conversion. It also describes how to
calculate actual voltage and current values based upon the digital data written to
CPU.
A/D Conversion Mechanism
This item describes the A/D conversion mechanism on the KV-AD4. Check this item
before writing sequence programs for the KV-AD4.
1. The analog signal (voltage or current) is input to the KV-AD4 from the external
instrument.
This operation is called "analog input."
2. The KV-AD4 converts the analog signal to digital data.
This operation is called "A/D conversion."
3. The KV-AD4 then writes the digital data to the data memory for A/D conversion
on the CPU.
Digital data is automatically written at each scan.
For details, see "About Digital Data after A/D Conversion" on the next page.
4. If necessary, the digital data is processed by the sequence program on the CPU.
The value of the actual input voltage or current can be calculated from the
digital data.
For details, see "Calculating Voltage and Current Values from Digital Data"on page 1-352.
The calculated values can be used for further processing besides the sequence program.
The digital data can also be output as analog data as it is.
Power
supply
unit
A/D
converter
KV-AD4
CPU
Writing digital data
Sequence
program
Data memory for
A/D conversion
Analog
input
Transducer
or
pre-amp
External
instrument
(e.g. sensor)
1
2
3
4
KVHKA Chap 09.p65 08.3.11, 11:20 AM350