Chapter 3 Use of Common Functions
3
34
When selecting "In-0"
5. Set the input value for correction point 1.
Use the
or key to set the desired numeric value.
• The value on the flashing digit can be changed.
• Pressing the
key changes the flashing digit to the right.
• Pressing the
key changes the value.
• All digits flash when the fifth digit and sign can be changed.
6. Press the
key to save the input value for correction point 1. Then, the sensor
enters the display value setting state.
The display value is displayed in green.
7. Set the display value for correction point 1 in the same procedure as step 5, and
use the
key to save the setting value.
8. Set and save the input and display values for correction point 2.
Repeat steps 5 and 6 to set and save the input and display values for
correction point 2.
After saving the display value for point 2, the sensor returns to the
measurement state.
No setting
(1st to 4th digits)
(5th digit)