Chapter 6 Normal Mode
58
6
3. Set the analog output function.
Press the button corresponding to the output for which the analog output func-
tion is to be set.
4. Press the [NEXT] button.
5. Press the [ANALOG OUTPUT] button.
Using the numeric keys, enter an analog output value in the location indicated
by the dotted line.
Note 1: When “-----” is displayed, the analog output is retained at +10 V.
Note 2: When the displayed value exceeds the preset scaling range, the analog
output is retained at +10 V. (When the displayed value falls below the scaling
range, the analog output is retained at -10 V.)
[Example]
When the analog output is set to “+10 V = 30.000” and “-10 V =
10.000”:
When the displayed value is 30 or more, the analog output is
retained at +10 V.
When the displayed value is 10 or less, the analog output is
retained at -10 V.
LASER ON OUTPUT MODE
NOR
MAL
P. 1
OUT1
OUT2
OUT3
I/O SLOT
SETUP
OUT4
ESC
Select Output to set.
OUTPUT MODEOUT1LASER ON P. 1
+A1 OFF OFF OFF
AREA1 AREA2 AREA3 AREA4
100
AVERAGE
CAL-
CULATE
1 (0.833ms)
MEASUR-
ING MODE
SELF-TIMING
INTERVAL (ms)
NORMAL
DIGIT
SUPPRESS
NONE
ESCHELP NEXT
NOR
MAL
OUTPUT MODEOUT1LASER ON P. 1
NOR
MAL
OFFSET
+10 V=
-10 V=
40.0000
0.0000
0.0000
ANALOG OUT
ESCPREV
OUTPUT MODEOUT1LASER ON P. 1
NOR
MAL
87
5 64
2 3
.-
1
0
9
ENTER
CANCEL
ESCAPE
OFFSET
+10 V=
-10 V=
40.0000
0.0000
0.0000
ANALOG OUT
Press [ESCAPE] to complete the entry.
Press [CANCEL] to cancel the entry.
The value returns to the previous value.