6-1 Troubleshooting
6
Appendix
6-3
- Digital Fiber Sensor FS-N10 Series User's Manual -
Preset related
A value less than "100.0" is dis-
played even when the [PRESET]
button is pressed.
The raw received light intensity is
50 or less. * (200 when using the
received light intensity expansion
setting.)
Press and hold the [MODE] button and check
the raw received light intensity level. Try adjust-
ing the beam axis, removing contamination, or
reviewing the installation environment. Take
actions to raise the original received light inten-
sity.
The maximum intensity is preset
with the received light intensity
almost saturated.
Preset the maximum intensity again after lower-
ing the received light intensity.
"Light emission/Received light intensity
adjustment (Saturation Canceling)" (page 3-18)
"Adjusting Light Emission/Received Light
Intensity (Attenuation)" (page 4-20)
When each preset function is exe-
cuted, "---- ----" appears, and no
change is seen.
The zero shift function is enabl
ed.
•Disable the ze
ro shift function.
"Zero Shift Function" (page 3-16)
The zero shift calibration (0SEt) is
selected as the sensitivity setting.
Select the sensitivity setting other than the zero
shift calibration.
"Sensitivity Setting" (page 4-4)
The rising / falling edge detection
mode is selected.
Select the detection method other than the rising
/ falling edge detection mode.
"Detection Mode" (page 4-8)
Zero shift input is selected with the
external input function.
Select a mode other than zero shift input for the
external input function.
"External Input" (page 4-17)
The difference in received light
intensity during preset function exe-
cution and workpiece preset func-
tion execution is small.
•Provide a sufficient difference in received light
intensity when using the preset function and
work-preset function.
The state was saturated when using
the maximum sensitivit
y preset
function and full auto pres
et func-
tion. The state was saturated when
using either the preset function or
workpiece preset function.
Make sure that the received light intensity does
not exceed the values listed in the
"Display Gain" (page 4-32).
Zero shift related
"---- ----" appears even when
using the zero shift function, and
each preset function with no effect
is being used.
The preset function is enabled.
Cancel each preset function.
"Preset Function" (page 3-6)
Preset input is selected with the
external input function.
Select a mode other than preset input with the
external input function.
"External Input" (page 4-17)
The rising edge detection/falling
edge detection mode is enabled.
Set a detection mode other than rising edge
detection/falling edge detection mode with the
detection mode settings.
"
Detection Mode" (page
4-8)
Nothing happens even when the
zero shift function is used.
The DATUM1/DATUM2 mode is
enabled.
Set a detection mode other than DATUM1/
DATUM2 mode with the detection mode set-
tings.
"Detection Mode" (page 4-8)
DATUM related
The received light intensity is not
calibrated to 100.0/.0 in the
DATUM1/2 modes.
The raw received light intensity is
50 or less. * (200 when using the
received light intensity expansion
setting FuLL)
Press and hold the [MODE] button and check
the raw received light intensity level. Try adjust-
ing the beam axis, removing contamination, or
reviewing the installation environment. Take
actions to raise the original received light inten-
sity.
The raw received light intensity is
less than the warning output level.
Check the installation environment and confirm
that the beam axis has not deviated and that the
workpiece surface is not contaminated.
To continue calibration, increase the warning out-
put level value. Calibration will not stop as fre-
quently.
Sensitivity set-
ting
(calibration)
related
Pressing the [SET] button has no
effect.
The sensitivity setting (calibration)
is restricted in specific detection
modes.
Change the detection mode or sensitivity setting
referring to
"Restrictions for Sensitivity Settings in
Each Detection Mode" (page 6-9).
Category Trouble Cause Action