Keyence DL-EP1 Manual de usuario Pagina 86

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 120
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 85
5-6
5
Appendix
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -
5-4
Procedures for Communicating with an Allen-Bradley ControlLogix PLC
This section explains the procedures for communicating with the DL-EP1 using an
Allen-Bradley ControlLogix PLC (EtherNet/IP scanner).
The DL-EP1 is capable of the following communication when connected to an Allen-
Bradley ControlLogix PLC.
Cyclic communication function maximum data size: 496 bytes
Message communication function: Class3/UCMM
Changing the cyclic communication settings
Refer to the PLC instruction manual for details on the PLC unit configuration and
settings such as RsLinx, required for communicating with the PC.
1
Select the EIP communication module (1756-ENBT) connected with the
DL-EP1 from RsLogix500 I/O Configuration, and then select "New Module"
with a right click.
Procedures for Communicating with an Allen-Bradley ControlLogix PLC
Vista de pagina 85
1 2 ... 81 82 83 84 85 86 87 88 89 90 91 ... 119 120

Comentarios a estos manuales

Sin comentarios