6.1 Interrupt Instructions
KV-300
KV-10/80
3-275
1
6
Chapter 6 Interrupts, High-speed Counters, Positioning Control
INT / RETI
Initial setting
When the operation is started, EI instruction enables interrupts.
Turning ON special utility relay 2203 allows CTC2 to reset the CTH1 current
value to 0.
The CTH1 current value is reset to 0.
The CTC2 preset value is set to 5000.
Turning ON special utility relay 2813 changes the input time constant to 10 µs.
Pulses input to 0005 are counted using CTH1.
When input 0000 turns ON, output 0501 is reset.
INT CTC2 is used to execute the interrupt. (Interrupt routine is executed when
the CTH1 current value and CTC2 preset value are equal.)
Immediate output to 0501 is performed.
Note 1: When the interrupt is executed, the contact of CTC2 is automatically reset.
Note 2: The operand used for INT instruction is not allowed for use with other INT
instructions.
KVNKA Chap 06.p65 08.3.11, 0:10 PM275