2.4 Instruction Details
3-146
2
Chapter 2 Instructions
CMP instruction compares the contents of the internal register with the value speci-
fied by the operand, and turns ON/OFF the special utility relays (2009, 2010, 2011)
according to the result of comparison.
Comparing the current value of the counter and CMP value
1) Output relay 0500 turns ON when the counter value is smaller than "1000" (C001
< #01000).
2) Output relay 0501 turns ON when the counter value is equal to "1000" (C001 =
#01000).
3) Output relay 0502 turns ON when the counter value is greater than "1000" (C001
> #01000).
4) Output relay 0503 turns ON when the counter value is equal to or greater than
"2000" (C001 #02000).
Coding
CMP: Compare
@CMP: Compare
Compares contents of internal register with
value specified by operand.
@
#,$
FUN
FUN
LDB
4
RES
0
LDB
4
RES
0
nnnn
CMP
nnnn
CMP
2009 2010 2011
(Internal register) < (Operand) ON OFF OFF
(Internal register) = (Operand) OFF ON OFF
(Internal register) > (Operand) OFF OFF ON
0001
C001
LDA
#01000
CMP
0500
#09999
0003
C001
2) (=)
1) (<)
3) (>)
4) ()
2002
C001
LDA
#02000
CMP
2002
2009
0501
2010
0502
2011
0503
2009
Line No. Instruction Operand Line No. Instruction Operand
0000 LDB 0001 0012 OUT 0501
0001 C 001 #099999 0003 0013 MPP
0002 LD 2002 0014 AND 2011
0003 LDA C001 0015 OUT 0502
0004 CON 0016 LD 2002
0005 CMP #01000 0017 LDA C001
0006 CON 0018 CON
0007 MPS 0019 CMP #02000
0008 AND 2009 0020 CON
0009 OUT 0500 0021 ANB 2009
0010 MRD 0022 OUT 0503
0011 AND 2010
:
:
CMP / @CMP
KVNKA Chap 02_4cP.p65 08.3.11, 0:02 PM146