14
Pressing and
U
at the same time will return to the
previous screen.
Initialization Value List
Item Default value (by model)
Model
GP-M
001
GP-M
010
GP-M
025
GP-M
100
GP-M
250
GP-M
400
Unit kPa MPa
SP1/FH1
(Switch-on point 1)
40.0 0.400 1.000 4.00 10.00 16.00
rP1/FL1
(Switch-off point 1)
20.0 0.200 0.500 2.00 5.00 8.00
SP2/FH2
(Switch-on point 2)
100.0 1.000 2.500 10.00 25.00 40.00
rP2/FL2
(Switch-off point 2)
80.0 0.800 2.000 8.00 20.00 32.00
ASP (Analog
start
point (4 mA))
-100.0 0.000 0.000 0.00 0.00 0.00
AEP (Analog
end
point (20 mA))
100.0 1.000 2.500 10.00 25.00 40.00
Item
Default value (for all models)
ou1 (detection mode of output 1) Hno
ou2 (detection mode of output 2) Hno
CoF (offset correction) No correction
dS1/dr1/dS2/dr2 (direct timer) 0.00 (s)
SPEd (responsiveness) 3 (ms)
Eco (power-save mode) oFF
HYS
(presence of hysterisis when in window mode)
on
diS.U (display renew cycle) 200 (ms)
diS.r (display inversion) no
PASS (password) 0000
Reference
MODE