4-3
4
Specifications
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
4-2
Data Processing Times
This section describes the length of time taken from detection by a sensor(s) to data
processing by PLC.
Maximum data processing time = (1) + (2) x 2 + (3) + (4)
(1) PLC scan time
(2) Network scan time
(3) Data communication time of DL-CL1
(4) Response time of sensor amplifier
(3) Data communication time of DL-CL1
The lengths of time taken for the data of output or current value to be sent from a
sensor amplifier to the DL-CL1 are summarized below.
For information on (1), (2), and (4), refer to the manual of each unit.
Number of sensor amplifier units connected Output, judgment value, or current value
19 ms
2 11 ms
3 15 ms
4 17 ms
CPU unit
CC-Link
master unit
DL-CL1
Sensor amplifier
(1) (2) (3) (4)