3-2 Device Maps
3-8
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Communicating with the FD-S series
3
Error information list
* "nn" denotes the ID number in hexadecimal of sensor amplifier. (Example: 01h for ID01, ..., 04h for
ID04)
If there are multiple errors, the smallest error code is stored in the remote register.
Command response list
Error
Information
(HEX)
*
Description Cause Corrective action
0000 No error - -
0001
0002
0005
Initialization error
Error encountered during
initialization.
Check the number of connected
sensor amplifiers and the
connection to the sensor
amplifiers, and then cycle power.
If the error remain, contact your
nearest sales office.
0003 Model error
There is connected a
sensor amplifier of a
model incompatible with
the DL-CL1.
Connect a sensor amplifier of a
compatible model.
0004 Mixed connection error
A foreign sensor amplifier
(i.e., one that cannot be
intermixed) is connected.
Remove the foreign sensor
amplifier.
0006 Number-of-units error
More sensor amplifiers are
connected than are
permitted.
Observe the number of
connectable sensor amplifiers.
0007 Sensor-to-sensor communication error
An error exists in the
communication between
sensor amplifiers.
Check the connections of the
sensor amplifiers, and then turn
off the power and back on.
nn01
Error 1 for sensor amplifier of ID number nn
(Not used)
Refer to the FD-S series
instruction manual.
nn02
Error 2 for sensor amplifier of ID number nn
Head connection error
nn03
Error 3 for sensor amplifier of ID number nn
Overcurrent error
nn04
Error 4 for sensor amplifier of ID number nn
EEPROM Error
nn05
Error 5 for sensor amplifier of ID number nn
Dry water error
nn06
Error 6 for sensor amplifier of ID number nn
Backflow error
nn07
Error 7 for sensor amplifier of ID number nn
(Not used)
nn08
Error 8 for sensor amplifier of ID number nn
(Not used)
nn09
Error 9 for sensor amplifier of ID number nn
(Not used)
nn0A
Error 10 for sensor amplifier of ID number nn
Drive gain error
nn0B
Error 11 for sensor amplifier of ID number nn
Te m p er ature low error
nn0C
Error 12 for sensor amplifier of ID number nn
Te m p er ature high error
Response
(HEX)
Name Description
0000 Successfully completed. The command has been processed successfully.
0001 Command number error The command number is out of range.
0002 Data category error The data category value is out of range.
0003 ID number out of range The ID number of sensor amplifier is out of range.
0004 Data number out of range The data number is out of range.
0007 Sensor-to-sensor communication error An error exists in the communication between sensors.
0008 Motion command access error Cannot read/write to motion command data numbers.
0009
Motion command data number out of range
The data number of motion command is out of range.
000A Motion command execution error Failed to execute the motion command.
000B Read inhibit Write-only data number. Cannot be read.