2-2 Wiring
2-8
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (FD-MH) -
2
Connection and Configuration
Connecting the cable
Use the following procedures to wire to the DeviceNet connector supplied with the DL-
DN1.
1
Connect the trimmed cable to the DeviceNet connector.
Insert the cable completely.
2
Attach the DeviceNet connector to the DL-DN1.
Plug the connector into the DL-DN1 and secure it down with the screws on each
end. (Tightening torque: 0.2 to 0.3 N•m)
Wire color Signal name Function
Black V -
Connects 0 VDC of the communication power supply.
BlueCAN_LCommunication signal (Low)
Bare wire SHIELD
Connects the shield of the DeviceNet cable.
White CAN_H Communication signal (High)
Red V +
Connects 24 VDC of the communication power supply.
Black
Blue
White
Red