4-3
4
Specifications
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -
4-2
Data Processing Times
This section describes the length of time taken from detection by a sensor(s) to data
processing by PLC.
Maximum data processing time = (1) + (2) x 2 + (3) + (4)
(1) PLC scan time
(2) Network scan time
(3) Data communication time of DL-CL1
(4) Response time of sensor amplifier
(3) Data communication time of DL-CL1
The lengths of time taken for the data of output or current value to be sent from a
sensor amplifier to the DL-CL1 are summarized below.
Sensor amplifier with calculation function OFF
Number of sensor amplifier units connected Output, judgment value, or current value
19 ms
2 11 ms
3 15 ms
4 17 ms
5 21 ms
6 23 ms
7 27 ms
8 29 ms
CPU unit
CC-Link
master unit
DL-CL1
Sensor amplifier
(1) (2) (3) (4)