3 Mount the attached end units (OP-26751: a set of two pieces) on both sides of the
sensor amplifier and the DeviceNet Compatible Network Unit DL-DN1, then fix
the end units with screws on the upper part of each end unit (2 points x 2 units).
The mounting method of the end unit is the same as that of the DeviceNet Compatible
Network Unit DL-DN1.
z Connecting to a panel mounting type sensor amplifier
1 Connect the sensor amplifier to the DeviceNet Compatible Network Unit DL-DN1
using the optional expansion cable (OP-35361).
2 Detach the sensor amplifier connector (for DIN rail mounting type) of the
DeviceNet Compatible Network Unit DL-DN1 with pliers and mount the attached
expansion connector sticker.
z Connecting to a large display type sensor amplifier
1 Connect the sensor amplifier to the DeviceNet Compatible Network Unit DL-DN1
using the optional expansion cable (OP-35361).
2 Detach the sensor amplifier connector (for DIN rail mounting type) of the
DeviceNet Compatible Network Unit DL-DN1 with pliers and mount the attached
expansion connector sticker.
Wiring
Use the following procedures to wire the DL-DN1.
Refer also to the DeviceNet Installation Manual published by ODVA.
Connecting to DeviceNet
Use the following procedure to connect the DL-DN1 to the DeviceNet.
z Recommended Cables
For connection between the DL-DN1 and the DeviceNet, use DeviceNet cables conform-
ing to the DeviceNet specifications or dedicated flat cables.
z Trimming the Cable
1 Strip the cable sheath.
Strip approximately 70 mm of cable sheath.
Make sure that the bare part of the shield braid is 6 mm or shorter.
2 Install shrinkable tube.
Cover the exposed sheathed conductors and the sheath using a shrinkable tube
approximately 40 mm long.
3 Strip the sheathed conductors.
Strip approximately 10 mm of sheath from the end of each conductor.
z Connecting the Cable
Use the following procedures to wire to the DeviceNet connector supplied with the DL-DN1.
1 Connect the trimmed cable to the DeviceNet connector.
Insert the cable completely.
2 Attach the DeviceNet connector to the DL-DN1.
Plug the connector into the DL-DN1 and secure it down with the screws on each end.
(Tightening torque: 0.2 to 0.3 Nm)
Be sure to insert the DeviceNet Compatible Network Unit DL-DN1
to the sensor amplifier to the end. Turning on the power with
diagonal insertion or improper insertion may damage the
equipment.
Turn OFF the power before connecting the expansion cable
and connect securely. Diagonal or otherwise improper
insertion may damage the equipment.
Inserting or pulling the cable when the power is turned ON
may damage the equipment.
Turn OFF the power before connecting the expansion cable
and connect securely. Diagonal or otherwise improper
insertion may damage the equipment.
Inserting or pulling the cable when the power is turned ON
may damage the equipment.
End unit
End unit
NOTICE
Detach the protection sticker
Expansion cable (cable length: 300 mm)
NOTICE
Sensor amplifier connector
(for DIN rail mounting type)
Expansion
connector sticker
Detach the
protection sticker
Detach the
protection
sticker
Expansion cable (cable length:300mm)
NOTICE
Sensor amplifier connector
(for DIN rail mounting type)
Expansion
connector sticker
Turn off the power before wiring.
To ensure normal communication, use only the DeviceNet or
dedicated cables.
If you are using solderless terminals, perform cable wiring /
trimming appropriately to suit the specifications of the
particular terminals.
Recommended solderless terminals: Phoenix Contact's A/AI
Series
Do not perform soldering (pre-soldering) on the trimmed
end of the cable.
Point
Point
6 mm or shorter
Approx. 70mm
Shield braid
Sheath
Approx. 40mm
Shrinkable tube
Sheath
Approx. 10mm
Sheathed conductor
Point
Wire color
Signal name
Function
Black
Connects 0 V of the
communication power supply.
Blue CAN_L Communication signal (Low)
Bare wire SHIELD
Connects the shield of the
DeviceNet cable.
White CAN_H Communication signal (High)
Red V+
V-
Connects 24 VDC of the
communication power supply.